For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations or direct buried. Résistant au soleil. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. Voltage 1000V CSA / 600V UL.
Cond. Dimensions | Cond. Strands | Diameter Over Conductor (in) (cm) | Épaisseur de l’isolation (mils) (mm) | Ground Size | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Rayon de courbure (pouces) (centimètres) | |
More Options |
500 KCMIL 500 KCMIL
|
35 35
|
0.735 1.87
|
90 2.29
|
1x1 1x1
|
115 2.92
|
2.565 6.52
|
80 2.03
|
2.731 6.94
|
3284 4887
|
9000 4082.33
|
19.1 48.51
|
More Options |
250 KCMIL 250 KCMIL
|
35 35
|
0.520 1.32
|
90 2.29
|
1x2 1x2
|
115 2.92
|
2.099 5.33
|
65 1.65
|
2.231 5.67
|
2104 3131
|
4500 2041.16
|
15.6 39.62
|
* Strand count meets minimum number per ASTM
Cond. Dimensions | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | |
More Options |
500 KCMIL 500 KCMIL
|
0.035 0.05
|
0.044 0.07
|
0.039 0.06
|
More Options |
250 KCMIL 250 KCMIL
|
0.071 0.11
|
0.086 0.13
|
0.041 0.06
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.