CSA TECK 90 1000V PVC CONTROL CABLE

1000V Multi Conductor, 14-10 AWG Copper, FT4 - Flame Retardancy Rating, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, -40°C - 90°C, Rated HL, AG14

Télécharger les spécifications de la catégorie
PDF Tableau Excel

Application & Features

For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Résistant au soleil. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.

  • -40°C - CSA Cold Bend and Impact Temperature
  • -40°C - Min. Installation Temperature
  • 90°C - Max. Continuous Operating Temperature

Spécifications

Pour plus d’informations, sélectionnez un ensemble de produits ci-dessous :
Cond. Dimensions Cond. Strands Diameter Over Conductor (in) (cm) Épaisseur de l’isolation (mils) (mm) Ground Size Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Épaisseur de la jaquette (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Rayon de courbure (pouces) (centimètres)
More Options
14 AWG 14 AWG
7 7
0.070 0.18
45 1.14
1x14 1x14
65 1.65
0.690 1.75
45 1.14
0.780 1.98
279 415
131 59.42
5.4 13.72
More Options
12 AWG 12 AWG
7 7
0.088 0.22
45 1.14
1x14 1x14
65 1.65
0.775 1.97
45 1.14
0.865 2.20
354 527
208 94.35
6.0 15.24
More Options
12 AWG 12 AWG
7 7
0.088 0.22
45 1.14
1x14 1x14
65 1.65
0.775 1.97
45 1.14
0.865 2.20
354 527
208 94.35
6.0 15.24
More Options
10 AWG 10 AWG
7 7
0.113 0.29
45 1.14
1x12 1x12
65 1.65
0.723 1.84
45 1.14
0.813 2.07
303 451
166 75.30
5.6 14.22
More Options
10 AWG 10 AWG
7 7
0.113 0.29
45 1.14
1x12 1x12
65 1.65
0.723 1.84
45 1.14
0.813 2.07
303 451
166 75.30
5.6 14.22
More Options
10 AWG 10 AWG
7 7
0.113 0.29
45 1.14
1x12 1x12
65 1.65
0.833 2.12
45 1.14
0.923 2.34
435 647
332 150.59
6.4 16.26
Cond. Dimensions DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km)
More Options
14 AWG 14 AWG
2.631 3.92
3.170 4.72
0.058 0.09
More Options
12 AWG 12 AWG
1.662 2.47
2.002 2.98
0.054 0.08
More Options
12 AWG 12 AWG
1.662 2.47
2.002 2.98
0.054 0.08
More Options
10 AWG 10 AWG
1.040 1.55
1.253 1.86
0.050 0.07
More Options
10 AWG 10 AWG
1.040 1.55
1.253 1.86
0.050 0.07
More Options
10 AWG 10 AWG
1.040 1.55
1.253 1.86
0.050 0.07

* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Normes et références

  • ASTM B3 Soft or Annealed Copper Wire
  • Conducteurs en cuivre toronné à couche concentrique ASTM B8
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • Test de résistance aux flammes IEEE 383 (70 000 btu)
  • Test de résistance aux flammes sur chemin de câbles vertical IEEE 1202 FT4 (70 000 Btu/h)

Construction

  1. Conducteur : Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
  2. Isolation : Cross-Linked Polyethylene (XLPE), Colour Code: 2/C black, white; 3/C red, black, blue; 4/C red, black, blue, white
  3. Grounding Conductors: Uninsulated Class B stranded grounding conductor
  4. Inner Jacket: Black Polyvinyl Chloride (PVC)
  5. Armor: Aluminum Interlocked Armour (AIA)
  6. Overall Jacket: Black PVC (optional colours available)

Ressources