Southwire’s Teck 90, 5000V, non-shielded, TRXLPE insulated (treeing resistant) power cable is a CSA approved armoured cable for industrial and commercial medium voltage applications. FT4, -40°C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and is concrete encaseable.
Cond. Dimensions | Cond. Strands | Diameter Over Conductor (in) (cm) | Épaisseur de l’isolation (mils) (mm) | Ground Size | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Rayon de courbure (pouces) (centimètres) | |
More Options |
2 AWG 2 AWG
|
7 7
|
0.282 0.72
|
90 2.29
|
1x6 1x6
|
85 2.16
|
1.585 4.03
|
55 1.40
|
1.695 4.31
|
1523 2266
|
1592 722.12
|
11.8 29.97
|
More Options |
1/0 AWG 1/0 AWG
|
19 19
|
0.361 0.92
|
90 2.29
|
1x6 1x6
|
85 2.16
|
1.764 4.48
|
55 1.40
|
1.874 4.76
|
2011 2993
|
2534 1149.40
|
13.1 33.27
|
More Options |
4/0 AWG 4/0 AWG
|
19 19
|
0.512 1.30
|
90 2.29
|
1x4 1x4
|
115 2.92
|
2.135 5.42
|
55 1.40
|
2.245 5.70
|
3448 5131
|
5078 2303.34
|
15.7 39.88
|
More Options |
250 KCMIL 250 KCMIL
|
37 37
|
0.558 1.42
|
90 2.29
|
1x4 1x4
|
115 2.92
|
2.282 5.80
|
65 1.65
|
2.414 6.13
|
3981 5924
|
6000 2721.55
|
16.8 42.67
|
More Options |
350 KCMIL 350 KCMIL
|
37 37
|
0.661 1.68
|
90 2.29
|
1x3 1x3
|
115 2.92
|
2.461 6.25
|
65 1.65
|
2.593 6.59
|
5095 7582
|
8400 3810.17
|
18.1 45.97
|
More Options |
500 KCMIL 500 KCMIL
|
37 37
|
0.789 2.00
|
90 2.29
|
1x3 1x3
|
115 2.92
|
2.731 6.94
|
65 1.65
|
2.863 7.27
|
6713 9990
|
12000 5443.10
|
20.0 50.80
|
More Options |
750 KCMIL 750 KCMIL
|
61 61
|
0.968 2.46
|
90 2.29
|
1x2 1x2
|
145 3.68
|
3.252 8.26
|
80 2.03
|
3.420 8.69
|
9801 14585
|
18000 8164.66
|
23.9 60.71
|
More Options |
2/0 AWG 2/0 AWG
|
19 19
|
0.405 1.03
|
90 2.29
|
1x6 1x6
|
85 2.16
|
1.869 4.75
|
55 1.40
|
1.979 5.03
|
2391 3558
|
3194 1448.77
|
13.8 35.05
|
* Other conductor sizes and outer jacket colours are available upon request. (#s in brackets represent # of strands / conductor. Number of strands may vary as per CSA standard.)
** Black Jacket
Cond. Dimensions | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity In Air 90C | |
More Options |
2 AWG 2 AWG
|
0.162 0.24
|
0.195 0.29
|
0.035 0.05
|
172 172
|
More Options |
1/0 AWG 1/0 AWG
|
0.102 0.15
|
0.122 0.18
|
0.033 0.05
|
225 225
|
More Options |
4/0 AWG 4/0 AWG
|
0.051 0.08
|
0.062 0.09
|
0.030 0.04
|
342 342
|
More Options |
250 KCMIL 250 KCMIL
|
0.043 0.06
|
0.053 0.08
|
0.030 0.04
|
376 376
|
More Options |
350 KCMIL 350 KCMIL
|
0.031 0.05
|
0.039 0.06
|
0.028 0.04
|
460 460
|
More Options |
500 KCMIL 500 KCMIL
|
0.022 0.03
|
0.029 0.04
|
0.027 0.04
|
556 556
|
More Options |
750 KCMIL 750 KCMIL
|
0.014 0.02
|
0.022 0.03
|
0.027 0.04
|
678 678
|
More Options |
2/0 AWG 2/0 AWG
|
0.081 0.12
|
0.097 0.14
|
0.032 0.05
|
260 260
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.