Southwire Type SER, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, the cable may be used in all applications where Type SE cable is permitted. Le câble de type SER peut être utilisé dans des endroits secs ou humides à des températures ne dépassant pas 90 °C. La tension nominale est de 600 volts. SE cables are not permitted underground, with or without a raceway, per NEC 338.12(A)(2).
Cond. Dimensions | Conductor Number | Diameter Over Conductor (in) (cm) | Cond. Strands | Épaisseur de l’isolation (mils) (mm) | Ground Size | Num x Neutral Size | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
8 AWG 8 AWG
|
3 3
|
0.128 0.33
|
Solid Solid
|
30 0.76
|
1x8 1x8
|
1x8 1x8
|
30 0.76
|
0.542 1.38
|
134 199
|
More Options |
6 AWG 6 AWG
|
2 2
|
0.169 0.43
|
7 7
|
30 0.76
|
1x6 1x6
|
1x6 1x6
|
30 0.76
|
0.599 1.52
|
144 214
|
More Options |
6 AWG 6 AWG
|
3 3
|
0.169 0.43
|
7 7
|
30 0.76
|
1x6 1x6
|
1x6 1x6
|
30 0.76
|
0.651 1.65
|
187 278
|
More Options |
4 AWG 4 AWG
|
2 2
|
0.212 0.54
|
7 7
|
45 1.14
|
1x6 1x6
|
1x6 1x6
|
30 0.76
|
0.738 1.87
|
190 283
|
More Options |
4 AWG 4 AWG
|
3 3
|
0.212 0.54
|
7 7
|
45 1.14
|
1x6 1x6
|
1x6 1x6
|
30 0.76
|
0.757 1.92
|
253 377
|
More Options |
2 AWG 2 AWG
|
3 3
|
0.268 0.68
|
6 6
|
45 1.14
|
1x4 1x4
|
1x4 1x4
|
30 0.76
|
0.895 2.27
|
361 537
|
More Options |
2 AWG 2 AWG
|
4 4
|
0.268 0.68
|
7 7
|
45 1.14
|
1x4 1x4
|
1x4 1x4
|
30 0.76
|
1.054 2.68
|
459 683
|
More Options |
1 AWG 1 AWG
|
3 3
|
0.298 0.76
|
8 8
|
55 1.40
|
1x3 1x3
|
1x3 1x3
|
30 0.76
|
1.078 2.74
|
460 685
|
More Options |
1/0 AWG 1/0 AWG
|
3 3
|
0.336 0.85
|
10 10
|
55 1.40
|
1x2 1x2
|
1x2 1x2
|
30 0.76
|
1.182 3.00
|
557 829
|
More Options |
2/0 AWG 2/0 AWG
|
3 3
|
0.376 0.96
|
12 12
|
55 1.40
|
1x1 1x1
|
1x1 1x1
|
30 0.76
|
1.279 3.25
|
670 997
|
More Options |
2/0 AWG 2/0 AWG
|
4 4
|
0.376 0.96
|
12 12
|
55 1.40
|
1x1 1x1
|
1x1 1x1
|
30 0.76
|
1.421 3.61
|
847 1260
|
More Options |
3/0 AWG 3/0 AWG
|
3 3
|
0.422 1.07
|
16 16
|
55 1.40
|
1x1/0 1x1/0
|
1x1/0 1x1/0
|
30 0.76
|
1.392 3.54
|
812 1208
|
More Options |
4/0 AWG 4/0 AWG
|
2 2
|
0.474 1.20
|
19 19
|
55 1.40
|
1x2/0 1x2/0
|
1x2/0 1x2/0
|
30 0.76
|
1.366 3.47
|
725 1079
|
More Options |
4/0 AWG 4/0 AWG
|
3 3
|
0.474 1.20
|
19 19
|
55 1.40
|
1x2/0 1x2/0
|
1x2/0 1x2/0
|
30 0.76
|
1.518 3.86
|
987 1469
|
More Options |
4/0 AWG 4/0 AWG
|
4 4
|
0.474 1.20
|
19 19
|
55 1.40
|
1x2/0 1x2/0
|
1x2/0 1x2/0
|
30 0.76
|
1.688 4.29
|
1251 1862
|
More Options |
250 KCMIL 250 KCMIL
|
3 3
|
0.520 1.32
|
22 22
|
65 1.65
|
1x3/0 1x3/0
|
1x3/0 1x3/0
|
30 0.76
|
1.670 4.24
|
1177 1752
|
More Options |
250 KCMIL 250 KCMIL
|
4 4
|
0.520 1.32
|
22 22
|
65 1.65
|
1x3/0 1x3/0
|
1x3/0 1x3/0
|
30 0.76
|
1.859 4.72
|
1491 2219
|
Cond. Dimensions | Conductor Number | Neutral Stranding (mils) (mm) | Min. Rayon de courbure (pouces) (centimètres) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
More Options |
8 AWG 8 AWG
|
3 3
|
|
2.2 5.59
|
297 134.72
|
0.653 0.97
|
0.786 1.17
|
0.052 0.08
|
40 40
|
45 45
|
More Options |
6 AWG 6 AWG
|
2 2
|
1 0.03
|
2.4 6.10
|
314 142.43
|
0.674 1.00
|
0.812 1.21
|
0.051 0.08
|
50 50
|
55 55
|
More Options |
6 AWG 6 AWG
|
3 3
|
1 0.03
|
2.6 6.60
|
472 214.10
|
0.674 1.00
|
0.812 1.21
|
0.051 0.08
|
50 50
|
55 55
|
More Options |
4 AWG 4 AWG
|
2 2
|
1 0.03
|
3.0 7.62
|
500 226.80
|
0.424 0.63
|
0.510 0.76
|
0.048 0.07
|
65 65
|
75 75
|
More Options |
4 AWG 4 AWG
|
3 3
|
1 0.03
|
3.0 7.62
|
751 340.65
|
0.424 0.63
|
0.510 0.76
|
0.048 0.07
|
65 65
|
75 75
|
More Options |
2 AWG 2 AWG
|
3 3
|
1 0.03
|
3.6 9.14
|
1194 541.59
|
0.267 0.40
|
0.321 0.48
|
0.045 0.07
|
90 90
|
100 100
|
More Options |
2 AWG 2 AWG
|
4 4
|
1 0.03
|
5.3 13.46
|
1274 577.88
|
0.267 0.40
|
0.321 0.48
|
0.045 0.07
|
72 72
|
80 80
|
More Options |
1 AWG 1 AWG
|
3 3
|
1 0.03
|
5.4 13.72
|
1506 683.11
|
0.211 0.31
|
0.254 0.38
|
0.046 0.07
|
100 100
|
115 115
|
More Options |
1/0 AWG 1/0 AWG
|
3 3
|
1 0.03
|
5.9 14.99
|
1900 861.82
|
0.168 0.25
|
0.201 0.30
|
0.044 0.07
|
120 120
|
135 135
|
More Options |
2/0 AWG 2/0 AWG
|
3 3
|
1 0.03
|
6.4 16.26
|
2395 1086.35
|
0.133 0.20
|
0.160 0.24
|
0.043 0.06
|
135 135
|
150 150
|
More Options |
2/0 AWG 2/0 AWG
|
4 4
|
1 0.03
|
7.1 18.03
|
2555 1158.93
|
0.133 0.20
|
0.160 0.24
|
0.043 0.06
|
108 108
|
120 120
|
More Options |
3/0 AWG 3/0 AWG
|
3 3
|
1 0.03
|
7.0 17.78
|
3020 1369.85
|
0.105 0.16
|
0.126 0.19
|
0.042 0.06
|
155 155
|
175 175
|
More Options |
4/0 AWG 4/0 AWG
|
2 2
|
1 0.03
|
6.8 17.27
|
2539 1151.67
|
0.084 0.13
|
0.100 0.15
|
0.041 0.06
|
180 180
|
205 205
|
More Options |
4/0 AWG 4/0 AWG
|
3 3
|
1 0.03
|
7.6 19.30
|
3808 1727.28
|
0.084 0.13
|
0.100 0.15
|
0.041 0.06
|
180 180
|
205 205
|
More Options |
4/0 AWG 4/0 AWG
|
4 4
|
1 0.03
|
8.4 21.34
|
4062 1842.49
|
0.084 0.13
|
0.100 0.15
|
0.041 0.06
|
144 144
|
164 164
|
More Options |
250 KCMIL 250 KCMIL
|
3 3
|
1 0.03
|
8.4 21.34
|
4500 2041.16
|
0.071 0.11
|
0.086 0.13
|
0.041 0.06
|
205 205
|
230 230
|
More Options |
250 KCMIL 250 KCMIL
|
4 4
|
1 0.03
|
9.3 23.62
|
4800 2177.24
|
0.071 0.11
|
0.086 0.13
|
0.041 0.06
|
164 164
|
184 184
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.