Southwire Type SER, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, the cable may be used in all applications where Type SE cable is permitted. Le câble de type SER peut être utilisé dans des endroits secs ou humides à des températures ne dépassant pas 90 °C. La tension nominale est de 600 volts. SE cables are not permitted underground, with or without a raceway, per NEC 338.12(A)(2).
Cond. Dimensions | Conductor Number | Diameter Over Conductor (in) (cm) | Cond. Strands | Épaisseur de l’isolation (mils) (mm) | Ground Size | Num x Neutral Size | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
6 AWG 6 AWG
|
3 3
|
0.177 0.45
|
7 7
|
45 1.14
|
1x6 1x6
|
1x6 1x6
|
30 0.76
|
0.710 1.80
|
421 627
|
More Options |
4 AWG 4 AWG
|
3 3
|
0.225 0.57
|
7 7
|
45 1.14
|
1x6 1x6
|
1x6 1x6
|
30 0.76
|
0.787 2.00
|
584 869
|
More Options |
3 AWG 3 AWG
|
3 3
|
0.252 0.64
|
7 7
|
45 1.14
|
1x5 1x5
|
1x5 1x5
|
30 0.76
|
0.855 2.17
|
718 1069
|
More Options |
2 AWG 2 AWG
|
3 3
|
0.282 0.72
|
7 7
|
45 1.14
|
1x4 1x4
|
1x4 1x4
|
30 0.76
|
0.933 2.37
|
886 1319
|
More Options |
1 AWG 1 AWG
|
3 3
|
0.322 0.82
|
19 19
|
55 1.40
|
1x3 1x3
|
1x3 1x3
|
30 0.76
|
1.131 2.87
|
1124 1673
|
More Options |
2/0 AWG 2/0 AWG
|
3 3
|
0.405 1.03
|
19 19
|
55 1.40
|
1x1 1x1
|
1x1 1x1
|
30 0.76
|
1.346 3.42
|
1730 2575
|
More Options |
3/0 AWG 3/0 AWG
|
3 3
|
0.456 1.16
|
19 19
|
55 1.40
|
1x1/0 1x1/0
|
1x1/0 1x1/0
|
30 0.76
|
1.462 3.71
|
2149 3198
|
Cond. Dimensions | Conductor Number | Neutral Stranding (mils) (mm) | Min. Rayon de courbure (pouces) (centimètres) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
More Options |
6 AWG 6 AWG
|
3 3
|
|
2.8 7.11
|
629 285.31
|
0.411 0.61
|
0.495 0.74
|
0.051 0.08
|
65 65
|
75 75
|
More Options |
4 AWG 4 AWG
|
3 3
|
1 0.03
|
3.1 7.87
|
1001 454.05
|
0.258 0.38
|
0.310 0.46
|
0.048 0.07
|
85 85
|
95 95
|
More Options |
3 AWG 3 AWG
|
3 3
|
1 0.03
|
3.4 8.64
|
1262 572.43
|
0.205 0.31
|
0.246 0.37
|
0.047 0.07
|
100 100
|
115 115
|
More Options |
2 AWG 2 AWG
|
3 3
|
1 0.03
|
3.7 9.40
|
1592 722.12
|
0.162 0.24
|
0.195 0.29
|
0.045 0.07
|
115 115
|
130 130
|
More Options |
1 AWG 1 AWG
|
3 3
|
1 0.03
|
5.7 14.48
|
2008 910.81
|
0.128 0.19
|
0.154 0.23
|
0.046 0.07
|
130 130
|
145 145
|
More Options |
2/0 AWG 2/0 AWG
|
3 3
|
1 0.03
|
6.7 17.02
|
3194 1448.77
|
0.081 0.12
|
0.097 0.14
|
0.043 0.06
|
175 175
|
195 195
|
More Options |
3/0 AWG 3/0 AWG
|
3 3
|
1 0.03
|
7.3 18.54
|
4027 1826.61
|
0.064 0.10
|
0.078 0.12
|
0.042 0.06
|
200 200
|
225 225
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.