SPEC: 44040

1/C CU 2000V EPR LSZH Exciter Cable

Single Conductor 2KV Flexible Class I Copper Ethylene Propylene Rubber Insulation Solonon® Low Smoke Zero Halogen (LSZH) Jacket

Télécharger les spécifications de la catégorie
PDF Tableau Excel

Application & Features

Southwire 2000V EPR/SOLONON Exciter Cable is suited for use in mass transit and general industry applications where flexibility, fire resistance, and low smoke generation are a concern. May be installed in wet or dry locations in cable trays or raceways. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Resistance to moisture and most oils, acids, and alkalis with an overall durable LSZH XLPO Thermoset Solonon® jacket. Alternate constructions available upon request.

Spécifications

Pour plus d’informations, sélectionnez un ensemble de produits ci-dessous :
Cond. Dimensions Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Épaisseur de l’isolation (mils) (mm) Épaisseur de la jaquette (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km)
More Options
1550 KCMIL 1550 KCMIL
0 0
3843 3843
1.596 4.05
150 3.81
115 2.92
2.132 5.42
5761 8573
Cond. Dimensions DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Min. Rayon de courbure (pouces) (centimètres)
More Options
1550 KCMIL 1550 KCMIL
0.008 0.01
0.012 0.02
0.035 0.05
12.7 32.26

† Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
† Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Normes et références

  • Spécification ASTM B172 relative aux conducteurs en cuivre toronnés à pose de câble ayant des conducteurs en cuivre toronnés en bande

Construction

  1. Conducteur : Flexible rope lay stranded annealed copper class I
  2. Ruban: Binder tape for ease of insulation removal
  3. Isolation : Heat, moisture, and ozone resistant Ethylene Propylene Rubber(EPR)
  4. Jaquette : SOLONON® Low Smoke Zero Halogen (LSZH) Thermoset Jacket

Ressources

Il n’existe aucune ressource téléchargeable pour ce produit.
Powered by Translations.com GlobalLink Web Software