Southwire’s 35KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. Ces câbles peuvent fonctionner en continu à une température de conducteur ne dépassant pas 105 °C pour un fonctionnement normal, 140 °C pour une surcharge d’urgence et 250 °C en des conditions de court-circuit. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. La jaquette en PVC intègre la technologie SIM et a un coefficient de friction COF de 0,2. Le câble peut être installé en conduit sans l’aide de lubrifiant. Classé pour 454 kg./Pression latérale maximale FT.
Cond. Dimensions | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Épaisseur de l’isolation (mils) (mm) | Diameter Over Shield (in) (cm) | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Rayon de courbure (pouces) (centimètres) | Conduit Size (in) (cm) | |
More Options |
4/0 AWG 4/0 AWG
|
19 19
|
0.474 1.20
|
1.203 3.06
|
345 8.76
|
1.263 3.21
|
80 2.03
|
1.443 3.67
|
1043 1552
|
1269 575.61
|
17.3 43.94
|
4.0 10.16
|
More Options |
500 KCMIL 500 KCMIL
|
35 35
|
0.735 1.87
|
1.494 3.79
|
345 8.76
|
1.554 3.95
|
110 2.79
|
1.794 4.56
|
1667 2481
|
3000 1360.78
|
21.5 54.61
|
5.0 12.70
|
More Options |
750 KCMIL 750 KCMIL
|
58 58
|
0.908 2.31
|
1.666 4.23
|
345 8.76
|
1.726 4.38
|
110 2.79
|
1.966 4.99
|
2064 3072
|
4500 2041.16
|
23.5 59.69
|
5.5 13.97
|
More Options |
1000 KCMIL 1000 KCMIL
|
58 58
|
1.060 2.69
|
1.818 4.62
|
345 8.76
|
1.878 4.77
|
110 2.79
|
2.128 5.41
|
2451 3647
|
6000 2721.55
|
25.5 64.77
|
6.0 15.24
|
* Strand count meets minimum number per ASTM
Cond. Dimensions | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
More Options |
4/0 AWG 4/0 AWG
|
0.084 0.13
|
0.105 0.16
|
0.048 0.07
|
0.047 0.07
|
0.445 + j0.274 0.445 + j0.274
|
0.106 + j0.046 0.106 + j0.046
|
3941 3941
|
230 230
|
245 245
|
310 310
|
345 345
|
More Options |
500 KCMIL 500 KCMIL
|
0.035 0.05
|
0.046 0.07
|
0.036 0.05
|
0.042 0.06
|
0.359 + j0.214 0.359 + j0.214
|
0.047 + j0.04 0.047 + j0.04
|
4774 4774
|
370 370
|
400 400
|
530 530
|
590 590
|
More Options |
750 KCMIL 750 KCMIL
|
0.024 0.04
|
0.033 0.05
|
0.031 0.05
|
0.039 0.06
|
0.329 + j0.184 0.329 + j0.184
|
0.034 + j0.038 0.034 + j0.038
|
5341 5341
|
455 455
|
490 490
|
685 685
|
765 765
|
More Options |
1000 KCMIL 1000 KCMIL
|
0.018 0.03
|
0.026 0.04
|
0.027 0.04
|
0.037 0.06
|
0.308 + j0.164 0.308 + j0.164
|
0.027 + j0.036 0.027 + j0.036
|
5812 5812
|
525 525
|
565 565
|
825 825
|
920 920
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.