Southwire’s 35KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. Ces câbles peuvent fonctionner en continu à une température de conducteur ne dépassant pas 105 °C pour un fonctionnement normal, 140 °C pour une surcharge d’urgence et 250 °C en des conditions de court-circuit. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. La jaquette en PVC intègre la technologie SIM et a un coefficient de friction COF de 0,2. Le câble peut être installé en conduit sans l’aide de lubrifiant. Classé pour 454 kg./Pression latérale maximale FT.
Cond. Dimensions | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Épaisseur de l’isolation (mils) (mm) | Diameter Over Shield (in) (cm) | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Rayon de courbure (pouces) (centimètres) | Conduit Size (in) (cm) | |
More Options |
1/0 AWG 1/0 AWG
|
10 10
|
0.336 0.85
|
1.214 3.08
|
420 10.67
|
1.274 3.24
|
80 2.03
|
1.454 3.69
|
998 1485
|
633 287.12
|
17.4 44.20
|
4.0 10.16
|
More Options |
2/0 AWG 2/0 AWG
|
12 12
|
0.376 0.96
|
1.254 3.19
|
420 10.67
|
1.314 3.34
|
80 2.03
|
1.494 3.79
|
1063 1582
|
798 361.97
|
17.9 45.47
|
4.5 11.43
|
More Options |
3/0 AWG 3/0 AWG
|
15 15
|
0.422 1.07
|
1.301 3.30
|
420 10.67
|
1.361 3.46
|
80 2.03
|
1.541 3.91
|
1141 1698
|
1006 456.31
|
18.4 46.74
|
4.5 11.43
|
More Options |
4/0 AWG 4/0 AWG
|
19 19
|
0.474 1.20
|
1.353 3.44
|
420 10.67
|
1.413 3.59
|
80 2.03
|
1.593 4.05
|
1233 1835
|
1269 575.61
|
19.1 48.51
|
4.5 11.43
|
More Options |
250 KCMIL 250 KCMIL
|
22 22
|
0.520 1.32
|
1.406 3.57
|
420 10.67
|
1.466 3.72
|
80 2.03
|
1.646 4.18
|
1323 1969
|
1500 680.39
|
19.7 50.04
|
5.0 12.70
|
More Options |
350 KCMIL 350 KCMIL
|
35 35
|
0.615 1.56
|
1.502 3.82
|
420 10.67
|
1.562 3.97
|
110 2.79
|
1.802 4.58
|
1611 2397
|
2100 952.54
|
21.6 54.86
|
5.0 12.70
|
More Options |
500 KCMIL 500 KCMIL
|
35 35
|
0.735 1.87
|
1.644 4.18
|
420 10.67
|
1.704 4.33
|
110 2.79
|
1.944 4.94
|
1899 2826
|
3000 1360.78
|
23.3 59.18
|
5.5 13.97
|
More Options |
750 KCMIL 750 KCMIL
|
58 58
|
0.908 2.31
|
1.816 4.61
|
420 10.67
|
1.876 4.77
|
110 2.79
|
2.126 5.40
|
2339 3481
|
4500 2041.16
|
25.5 64.77
|
6.0 15.24
|
More Options |
1000 KCMIL 1000 KCMIL
|
58 58
|
1.060 2.69
|
1.968 5.00
|
420 10.67
|
2.028 5.15
|
110 2.79
|
2.278 5.79
|
2722 4051
|
6000 2721.55
|
27.3 69.34
|
|
More Options |
1250 KCMIL 1250 KCMIL
|
91 91
|
1.250 3.18
|
2.171 5.51
|
420 10.67
|
2.231 5.67
|
110 2.79
|
2.471 6.28
|
3174 4723
|
7500 3401.94
|
29.6 75.18
|
|
* Strand count meets minimum number per ASTM
! Made with Aluminum 1350
Cond. Dimensions | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
More Options |
1/0 AWG 1/0 AWG
|
0.168 0.25
|
0.211 0.31
|
0.067 0.10
|
0.055 0.08
|
0.55 + j0.279 0.55 + j0.279
|
0.212 + j0.054 0.212 + j0.054
|
3978 3978
|
155 155
|
165 165
|
200 200
|
225 225
|
More Options |
2/0 AWG 2/0 AWG
|
0.133 0.20
|
0.167 0.25
|
0.062 0.09
|
0.053 0.08
|
0.502 + j0.268 0.502 + j0.268
|
0.168 + j0.052 0.168 + j0.052
|
4102 4102
|
175 175
|
190 190
|
230 230
|
260 260
|
More Options |
3/0 AWG 3/0 AWG
|
0.105 0.16
|
0.133 0.20
|
0.058 0.09
|
0.051 0.08
|
0.464 + j0.257 0.464 + j0.257
|
0.134 + j0.05 0.134 + j0.05
|
4244 4244
|
200 200
|
215 215
|
270 270
|
300 300
|
More Options |
4/0 AWG 4/0 AWG
|
0.084 0.13
|
0.105 0.16
|
0.054 0.08
|
0.050 0.07
|
0.431 + j0.244 0.431 + j0.244
|
0.106 + j0.048 0.106 + j0.048
|
4405 4405
|
230 230
|
245 245
|
310 310
|
345 345
|
More Options |
250 KCMIL 250 KCMIL
|
0.071 0.11
|
0.090 0.13
|
0.051 0.08
|
0.048 0.07
|
0.41 + j0.233 0.41 + j0.233
|
0.091 + j0.047 0.091 + j0.047
|
4573 4573
|
250 250
|
270 270
|
345 345
|
380 380
|
More Options |
350 KCMIL 350 KCMIL
|
0.050 0.07
|
0.065 0.10
|
0.046 0.07
|
0.046 0.07
|
0.375 + j0.214 0.375 + j0.214
|
0.066 + j0.045 0.066 + j0.045
|
4867 4867
|
305 305
|
330 330
|
430 430
|
475 475
|
More Options |
500 KCMIL 500 KCMIL
|
0.035 0.05
|
0.046 0.07
|
0.041 0.06
|
0.044 0.07
|
0.345 + j0.193 0.345 + j0.193
|
0.047 + j0.042 0.047 + j0.042
|
5239 5239
|
370 370
|
400 400
|
530 530
|
590 590
|
More Options |
750 KCMIL 750 KCMIL
|
0.024 0.04
|
0.033 0.05
|
0.035 0.05
|
0.041 0.06
|
0.315 + j0.167 0.315 + j0.167
|
0.034 + j0.039 0.034 + j0.039
|
5806 5806
|
455 455
|
490 490
|
685 685
|
765 765
|
More Options |
1000 KCMIL 1000 KCMIL
|
0.018 0.03
|
0.026 0.04
|
0.031 0.05
|
0.039 0.06
|
0.295 + j0.15 0.295 + j0.15
|
0.027 + j0.038 0.027 + j0.038
|
6277 6277
|
525 525
|
565 565
|
825 825
|
920 920
|
More Options |
1250 KCMIL 1250 KCMIL
|
0.014 0.02
|
0.023 0.03
|
0.028 0.04
|
0.037 0.06
|
0.276 - j0.124 0.276 - j0.124
|
0.024 - j0.219 0.024 - j0.219
|
6878 6878
|
595 595
|
640 640
|
950 950
|
1055 1055
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.