SPEC: 46110

AL Compact 5/8kV NLEPR Insulation 133/100% IL SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial

Type MV-105 Single Conductor Aluminum, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Télécharger les spécifications de la catégorie
PDF Tableau Excel

Application & Features

Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. Ces câbles peuvent fonctionner en continu à une température de conducteur ne dépassant pas 105 °C pour un fonctionnement normal, 140 °C pour une surcharge d’urgence et 250 °C en des conditions de court-circuit. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. La jaquette en PVC intègre la technologie SIM et a un coefficient de friction COF de 0,2. Le câble peut être installé en conduit sans l’aide de lubrifiant. Classé pour 454 kg./Pression latérale maximale FT.

Spécifications

Pour plus d’informations, sélectionnez un ensemble de produits ci-dessous :
Cond. Dimensions Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Épaisseur de l’isolation (mils) (mm) Diameter Over Shield (in) (cm) Épaisseur de la jaquette (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Rayon de courbure (pouces) (centimètres) Conduit Size (in) (cm)
More Options
2 AWG 2 AWG
7 7
0.268 0.68
0.536 1.36
115 2.92
0.640 1.63
55 1.40
0.790 2.01
342 509
398 180.53
9.4 23.88
2.5 6.35
More Options
1/0 AWG 1/0 AWG
10 10
0.336 0.85
0.604 1.53
115 2.92
0.664 1.69
55 1.40
0.814 2.07
377 561
633 287.12
9.7 24.64
2.5 6.35
More Options
2/0 AWG 2/0 AWG
12 12
0.376 0.96
0.644 1.64
115 2.92
0.704 1.79
80 2.03
0.884 2.25
446 664
798 361.97
10.6 26.92
2.5 6.35
More Options
4/0 AWG 4/0 AWG
19 19
0.474 1.20
0.743 1.89
115 2.92
0.803 2.04
80 2.03
0.983 2.50
569 847
1269 575.61
11.7 29.72
3.0 7.62
More Options
350 KCMIL 350 KCMIL
35 35
0.615 1.56
0.892 2.27
115 2.92
0.952 2.42
80 2.03
1.132 2.88
777 1156
2100 952.54
13.5 34.29
3.5 8.89
More Options
500 KCMIL 500 KCMIL
35 35
0.735 1.87
1.034 2.63
115 2.92
1.094 2.78
80 2.03
1.274 3.24
990 1473
3000 1360.78
15.2 38.61
3.5 8.89
More Options
750 KCMIL 750 KCMIL
58 58
0.908 2.31
1.206 3.06
115 2.92
1.266 3.22
80 2.03
1.446 3.67
1315 1957
4500 2041.16
17.3 43.94
4.0 10.16
More Options
1000 KCMIL 1000 KCMIL
58 58
1.060 2.69
1.044 2.65
115 2.92
1.104 2.80
80 2.03
1.598 4.06
1627 2421
6000 2721.55
19.1 48.51
4.5 11.43

* Strand count meets minimum number per ASTM

Cond. Dimensions DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Capacitive Reactance (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles Allowable Ampacity In Duct 90C Allowable Ampacity In Duct 105C Allowable Ampacity In Air 90C Allowable Ampacity In Air 105C
More Options
2 AWG 2 AWG
0.267 0.40
0.336 0.50
0.036 0.05
0.045 0.07
0.7 + j0.521 0.7 + j0.521
0.336 + j0.044 0.336 + j0.044
1877 1877
115 115
125 125
150 150
165 165
More Options
1/0 AWG 1/0 AWG
0.168 0.25
0.211 0.31
0.030 0.04
0.041 0.06
0.581 + j0.482 0.581 + j0.482
0.211 + j0.04 0.211 + j0.04
2088 2088
150 150
160 160
200 200
225 225
More Options
2/0 AWG 2/0 AWG
0.133 0.20
0.167 0.25
0.028 0.04
0.041 0.06
0.537 + j0.46 0.537 + j0.46
0.167 + j0.04 0.167 + j0.04
2212 2212
170 170
185 185
230 230
260 260
More Options
4/0 AWG 4/0 AWG
0.084 0.13
0.105 0.16
0.023 0.03
0.038 0.06
0.476 + j0.413 0.476 + j0.413
0.105 + j0.037 0.105 + j0.037
2515 2515
225 225
245 245
310 310
350 350
More Options
350 KCMIL 350 KCMIL
0.050 0.07
0.065 0.10
0.019 0.03
0.036 0.05
0.43 + j0.352 0.43 + j0.352
0.066 + j0.034 0.066 + j0.034
2977 2977
305 305
325 325
430 430
480 480
More Options
500 KCMIL 500 KCMIL
0.035 0.05
0.046 0.07
0.016 0.02
0.034 0.05
0.403 + j0.312 0.403 + j0.312
0.047 + j0.032 0.047 + j0.032
3349 3349
370 370
400 400
545 545
605 605
More Options
750 KCMIL 750 KCMIL
0.024 0.04
0.033 0.05
0.014 0.02
0.032 0.05
0.374 + j0.261 0.374 + j0.261
0.034 + j0.031 0.034 + j0.031
3916 3916
470 470
505 505
710 710
790 790
More Options
1000 KCMIL 1000 KCMIL
0.018 0.03
0.026 0.04
0.012 0.02
0.031 0.05
0.352 + j0.227 0.352 + j0.227
0.027 + j0.03 0.027 + j0.03
4387 4387
545 545
590 590
855 855
950 950

* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.

Normes et références

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Conducteurs en aluminium ronds compacts et toronnés
  • UL 1072 Câbles d’alimentation à moyen voltage
  • UL 1685 FT4 Test de propagation des flammes et émission de fumées sur chemin vertical (1/0 et plus grands)
  • CSA C22.2 N° 230 Chemins de câble TC-ER (1/0 AWG et plus grands)
  • CSA C22.2 N° 2556 / UL 2556 Méthodes de test des câbles
  • CSA C68.10 Câbles d’alimentation blindés pour application commerciales et industrielles de 5 à 46 KV
  • ICEA S-93-639 (NEMA WC 74) Câbles d’alimentation blindés de 5 à 46 KV
  • Norme ICEA S-97-682 pour les câbles utilitaires blindés ayant des tensions nominales de 5 à 46 kV
  • IEEE 1202 FT4 Test de résistance aux flammes (70 000 Btu/h) sur chemin de câbles vertical (1/0 et plus grands)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • FABRIQUÉ AUX ÉTATS-UNIS : Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conducteur : Aluminium compact toronné Série 8 000 de catégorie B conformément aux normes ASTM B800 et ASTM B836
  2. Conductor Shield: Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Isolation : 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level,
  4. Insulation Shield: Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield: Helically wrapped 5 mil copper tape with 25% overlap
  6. Overall Jacket: Chlorure de polyvinyle (PVC)