Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. Ces câbles peuvent fonctionner en continu à une température de conducteur ne dépassant pas 105 °C pour un fonctionnement normal, 140 °C pour une surcharge d’urgence et 250 °C en des conditions de court-circuit. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. La jaquette en PVC intègre la technologie SIM et a un coefficient de friction COF de 0,2. Le câble peut être installé en conduit sans l’aide de lubrifiant. Classé pour 454 kg./Pression latérale maximale FT.
Cond. Dimensions | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Épaisseur de l’isolation (mils) (mm) | Diameter Over Shield (in) (cm) | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Rayon de courbure (pouces) (centimètres) | Conduit Size (in) (cm) | |
More Options |
2 AWG 2 AWG
|
7 7
|
0.282 0.72
|
0.665 1.69
|
175 4.45
|
0.725 1.84
|
80 2.03
|
0.911 2.31
|
569 847
|
530 240.40
|
10.9 27.69
|
2.5 6.35
|
More Options |
350 KCMIL 350 KCMIL
|
37 37
|
0.661 1.68
|
1.037 2.63
|
175 4.45
|
1.097 2.79
|
80 2.03
|
1.277 3.24
|
1661 2472
|
2800 1270.06
|
15.3 38.86
|
3.5 8.89
|
More Options |
750 KCMIL 750 KCMIL
|
61 61
|
0.968 2.46
|
1.404 3.57
|
175 4.45
|
1.464 3.72
|
80 2.03
|
1.644 4.18
|
3129 4656
|
6000 2721.55
|
19.7 50.04
|
5.0 12.70
|
More Options |
1000 KCMIL 1000 KCMIL
|
61 61
|
1.117 2.84
|
1.523 3.87
|
175 4.45
|
1.583 4.02
|
110 2.79
|
1.823 4.63
|
4063 6046
|
8000 3628.74
|
21.8 55.37
|
5.0 12.70
|
More Options |
500 KCMIL 500 KCMIL
|
37 37
|
0.789 2.00
|
1.162 2.95
|
175 4.45
|
1.222 3.10
|
80 2.03
|
1.402 3.56
|
2198 3271
|
4000 1814.37
|
16.8 42.67
|
4.0 10.16
|
* Conduit size based on 3 phase 40% fill-factor without ground
Cond. Dimensions | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
More Options |
2 AWG 2 AWG
|
0.162 0.24
|
0.204 0.30
|
0.044 0.07
|
0.049 0.07
|
0.575 + j0.458 0.575 + j0.458
|
0.204 + j0.05 0.204 + j0.05
|
2292 2292
|
155 155
|
165 165
|
195 195
|
215 215
|
More Options |
350 KCMIL 350 KCMIL
|
0.031 0.05
|
0.041 0.06
|
0.024 0.04
|
0.037 0.06
|
0.394 + j0.303 0.394 + j0.303
|
0.042 + j0.037 0.042 + j0.037
|
3491 3491
|
390 390
|
415 415
|
550 550
|
610 610
|
More Options |
750 KCMIL 750 KCMIL
|
0.014 0.02
|
0.023 0.03
|
0.018 0.03
|
0.033 0.05
|
0.346 + j0.225 0.346 + j0.225
|
0.024 + j0.033 0.024 + j0.033
|
4473 4473
|
565 565
|
610 610
|
885 885
|
990 990
|
More Options |
1000 KCMIL 1000 KCMIL
|
0.011 0.02
|
0.019 0.03
|
0.016 0.02
|
0.033 0.05
|
0.327 + j0.198 0.327 + j0.198
|
0.02 + j0.033 0.02 + j0.033
|
4935 4935
|
640 640
|
690 690
|
1060 1060
|
1185 1185
|
More Options |
500 KCMIL 500 KCMIL
|
0.022 0.03
|
0.030 0.04
|
0.021 0.03
|
0.035 0.05
|
0.372 + j0.268 0.372 + j0.268
|
0.031 + j0.035 0.031 + j0.035
|
3888 3888
|
465 465
|
500 500
|
685 685
|
765 765
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.