SPEC: 46325

CU Compressed 15kV NLEPR Insulation 133% IL Black SIM-PVC Jacket. MV 105 - 2x5 mils Tape Shield -Tray Rated - Sunlight Resistant - For Direct Burial

Type MV-105 Single Conductor Copper, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, 2x5 Mils Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Télécharger les spécifications de la catégorie
PDF Tableau Excel

Application & Features

Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. Ces câbles peuvent fonctionner en continu à une température de conducteur ne dépassant pas 105 °C pour un fonctionnement normal, 140 °C pour une surcharge d’urgence et 250 °C en des conditions de court-circuit. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. La jaquette en PVC intègre la technologie SIM et a un coefficient de friction COF de 0,2. Le câble peut être installé en conduit sans l’aide de lubrifiant. Classé pour 454 kg./Pression latérale maximale FT.

Spécifications

Pour plus d’informations, sélectionnez un ensemble de produits ci-dessous :
Cond. Dimensions Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Épaisseur de l’isolation (mils) (mm) Diameter Over Shield (in) (cm) Épaisseur de la jaquette (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Rayon de courbure (pouces) (centimètres) Conduit Size (in) (cm)
More Options
350 KCMIL 350 KCMIL
37 37
0.661 1.68
1.127 2.86
220 5.59
1.187 3.01
80 2.03
1.387 3.52
1861 2769
2800 1270.06
16.6 42.16
4.0 10.16
More Options
750 KCMIL 750 KCMIL
61 61
0.968 2.46
1.464 3.72
220 5.59
1.524 3.87
110 2.79
1.784 4.53
3448 5131
6000 2721.55
21.4 54.36
5.0 12.70
More Options
1000 KCMIL 1000 KCMIL
61 61
1.117 2.84
1.613 4.10
220 5.59
1.673 4.25
110 2.79
1.933 4.91
4339 6457
8000 3628.74
23.1 58.67
5.5 13.97

* Conduit size based on 3 phase 40% fill-factor without ground

Cond. Dimensions DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Capacitive Reactance (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles Allowable Ampacity In Duct 90C Allowable Ampacity In Duct 105C Allowable Ampacity In Air 90C Allowable Ampacity In Air 105C
More Options
350 KCMIL 350 KCMIL
0.031 0.05
0.041 0.06
0.028 0.04
0.039 0.06
0.386 + j0.281 0.386 + j0.281
0.042 + j0.039 0.042 + j0.039
3770 3770
390 390
415 415
550 550
610 610
More Options
750 KCMIL 750 KCMIL
0.014 0.02
0.023 0.03
0.021 0.03
0.035 0.05
0.337 + j0.211 0.337 + j0.211
0.024 + j0.035 0.024 + j0.035
4752 4752
565 565
610 610
885 885
990 990
More Options
1000 KCMIL 1000 KCMIL
0.011 0.02
0.019 0.03
0.019 0.03
0.034 0.05
0.319 + j0.186 0.319 + j0.186
0.02 + j0.034 0.02 + j0.034
5214 5214
640 640
690 690
1060 1060
1185 1185

* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.

Normes et références

  • ASTM B3 Soft or Annealed Copper Wire
  • Conducteurs en cuivre toronné à couche concentrique ASTM B8
  • Spécification ASTM B33 relative au fil de cuivre étamé mou ou recuit
  • UL 1072 Câbles d’alimentation à moyen voltage
  • UL 1685 FT4 Test de propagation des flammes et émission de fumées sur chemin vertical (1/0 et plus grands)
  • CSA C22.2 N° 230 Chemins de câble TC-ER (1/0 AWG et plus grands)
  • CSA C22.2 N° 2556 / UL 2556 Méthodes de test des câbles
  • CSA C68.10 Câbles d’alimentation blindés pour application commerciales et industrielles de 5 à 46 KV
  • ICEA S-93-639 (NEMA WC 74) Câbles d’alimentation blindés de 5 à 46 KV
  • IEEE 1202 FT4 Test de résistance aux flammes (70 000 Btu/h) sur chemin de câbles vertical (1/0 et plus grands)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • FABRIQUÉ AUX ÉTATS-UNIS : Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conducteur : Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (Tinned Copper per ASTM B33 optional)
  2. Conductor Shield: Semi-conducting cross-linked copolymer
  3. Isolation : 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level,
  4. Insulation Shield: Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield: Helically wrapped 2x5 mil copper tape with 25% overlap
  6. Overall Jacket: Chlorure de polyvinyle (PVC)