SPEC: 46702

CU Compressed 35kV NLEPR Insulation 133% IL Black SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial

Type MV-105 Single Conductor Copper, 420 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Télécharger les spécifications de la catégorie
PDF Tableau Excel

Application & Features

Southwire’s 35KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. Ces câbles peuvent fonctionner en continu à une température de conducteur ne dépassant pas 105 °C pour un fonctionnement normal, 140 °C pour une surcharge d’urgence et 250 °C en des conditions de court-circuit. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. La jaquette en PVC intègre la technologie SIM et a un coefficient de friction COF de 0,2. Le câble peut être installé en conduit sans l’aide de lubrifiant. Classé pour 454 kg./Pression latérale maximale FT.

Spécifications

Pour plus d’informations, sélectionnez un ensemble de produits ci-dessous :
Cond. Dimensions Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Épaisseur de l’isolation (mils) (mm) Diameter Over Shield (in) (cm) Épaisseur de la jaquette (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Rayon de courbure (pouces) (centimètres) Conduit Size (in) (cm)
More Options
1/0 AWG 1/0 AWG
19 19
0.361 0.92
1.240 3.15
420 10.67
1.300 3.30
80 2.03
1.480 3.76
1249 1859
844 382.83
17.7 44.96
4.5 11.43
More Options
2/0 AWG 2/0 AWG
19 19
0.405 1.03
1.284 3.26
420 10.67
1.344 3.41
80 2.03
1.524 3.87
1377 2049
1064 482.62
18.2 46.23
4.5 11.43
More Options
4/0 AWG 4/0 AWG
19 19
0.512 1.30
1.390 3.53
420 10.67
1.450 3.68
80 2.03
1.630 4.14
1721 2561
1692 767.48
19.6 49.78
4.5 11.43
More Options
250 KCMIL 250 KCMIL
37 37
0.558 1.42
1.428 3.63
420 10.67
1.488 3.78
110 2.79
1.728 4.39
1983 2951
2000 907.18
20.7 52.58
5.0 12.70
More Options
350 KCMIL 350 KCMIL
37 37
0.661 1.68
1.527 3.88
420 10.67
1.587 4.03
110 2.79
1.827 4.64
2385 3549
2800 1270.06
21.9 55.63
5.5 13.97
More Options
500 KCMIL 500 KCMIL
37 37
0.789 2.00
1.652 4.20
420 10.67
1.712 4.35
110 2.79
1.952 4.96
2976 4429
4000 1814.37
23.4 59.44
5.5 13.97
More Options
750 KCMIL 750 KCMIL
61 61
0.968 2.46
1.864 4.73
420 10.67
1.924 4.89
110 2.79
2.164 5.50
3972 5911
6000 2721.55
25.9 65.79
6.0 15.24
More Options
1250 KCMIL 1250 KCMIL
91 91
1.250 3.18
2.150 5.46
420 10.67
2.210 5.61
110 2.79
2.450 6.22
5816 8655
10000 4535.92
29.4 74.68
More Options
250 KCMIL 250 KCMIL
37 37
0.558 1.42
1.428 3.63
420 10.67
1.488 3.78
110 2.79
1.728 4.39
1975 2939
2000 907.18
20.7 52.58
5.0 12.70

* Conduit size based on 3 phase 40% fill-factor without ground

^ Non SimPull Jacket. Non CSA listed.

Cond. Dimensions DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Capacitive Reactance (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles Allowable Ampacity In Duct 90C Allowable Ampacity In Duct 105C Allowable Ampacity In Air 90C Allowable Ampacity In Air 105C
More Options
1/0 AWG 1/0 AWG
0.102 0.15
0.128 0.19
0.064 0.10
0.054 0.08
0.465 + j0.274 0.465 + j0.274
0.129 + j0.054 0.129 + j0.054
4055 4055
200 200
215 215
260 260
290 290
More Options
2/0 AWG 2/0 AWG
0.081 0.12
0.102 0.15
0.060 0.09
0.052 0.08
0.434 + j0.263 0.434 + j0.263
0.103 + j0.052 0.103 + j0.052
4192 4192
230 230
245 245
300 300
330 330
More Options
4/0 AWG 4/0 AWG
0.051 0.08
0.065 0.10
0.050 0.07
0.048 0.07
0.387 + j0.237 0.387 + j0.237
0.066 + j0.049 0.066 + j0.049
4523 4523
295 295
315 315
395 395
445 445
More Options
250 KCMIL 250 KCMIL
0.043 0.06
0.056 0.08
0.049 0.07
0.048 0.07
0.372 + j0.227 0.372 + j0.227
0.057 + j0.048 0.057 + j0.048
4690 4690
325 325
345 345
440 440
490 490
More Options
350 KCMIL 350 KCMIL
0.031 0.05
0.041 0.06
0.044 0.07
0.045 0.07
0.347 + j0.207 0.347 + j0.207
0.042 + j0.045 0.042 + j0.045
5009 5009
390 390
415 415
545 545
605 605
More Options
500 KCMIL 500 KCMIL
0.022 0.03
0.030 0.04
0.039 0.06
0.043 0.06
0.324 + j0.187 0.324 + j0.187
0.031 + j0.043 0.031 + j0.043
5406 5406
465 465
500 500
680 680
755 755
More Options
750 KCMIL 750 KCMIL
0.014 0.02
0.023 0.03
0.034 0.05
0.040 0.06
0.3 + j0.161 0.3 + j0.161
0.024 + j0.04 0.024 + j0.04
5992 5992
565 565
610 610
870 870
970 970
More Options
1250 KCMIL 1250 KCMIL
0.009 0.01
0.018 0.03
0.028 0.04
0.037 0.06
0.271 - j0.124 0.271 - j0.124
0.019 - j0.219 0.019 - j0.219
6878 6878
715 715
770 770
1185 1185
1320 1320
More Options
250 KCMIL 250 KCMIL
0.043 0.06
0.056 0.08
0.049 0.07
0.048 0.07
0.372 + j0.227 0.372 + j0.227
0.057 + j0.048 0.057 + j0.048
4690 4690
325 325
345 345
440 440
490 490

* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.

Normes et références

  • ASTM B3 Soft or Annealed Copper Wire
  • Conducteurs en cuivre toronné à couche concentrique ASTM B8
  • Spécification ASTM B33 relative au fil de cuivre étamé mou ou recuit
  • UL 1072 Câbles d’alimentation à moyen voltage
  • UL 1685 FT4 Test de propagation des flammes et émission de fumées sur chemin vertical (1/0 et plus grands)
  • CSA C22.2 N° 230 Chemins de câble TC-ER (1/0 AWG et plus grands)
  • CSA C22.2 N° 2556 / UL 2556 Méthodes de test des câbles
  • CSA C68.10 Câbles d’alimentation blindés pour application commerciales et industrielles de 5 à 46 KV
  • ICEA S-93-639 (NEMA WC 74) Câbles d’alimentation blindés de 5 à 46 KV
  • Norme ICEA S-97-682 pour les câbles utilitaires blindés ayant des tensions nominales de 5 à 46 kV
  • IEEE 1202 FT4 Test de résistance aux flammes (70 000 Btu/h) sur chemin de câbles vertical (1/0 et plus grands)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • FABRIQUÉ AUX ÉTATS-UNIS : Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conducteur : Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (Tinned Copper per ASTM B33 optional)
  2. Conductor Shield: Semi-conducting cross-linked copolymer
  3. Isolation : 420 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level,
  4. Insulation Shield: Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield: Helically wrapped 5 mil copper tape with 25% overlap
  6. Overall Jacket: Sunlight resistant Polyvinyl Chloride (PVC)