Southwire’s 35KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. Ces câbles peuvent fonctionner en continu à une température de conducteur ne dépassant pas 105 °C pour un fonctionnement normal, 140 °C pour une surcharge d’urgence et 250 °C en des conditions de court-circuit. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. La jaquette en PVC intègre la technologie SIM et a un coefficient de friction COF de 0,2. Le câble peut être installé en conduit sans l’aide de lubrifiant. Classé pour 454 kg./Pression latérale maximale FT.
Cond. Dimensions | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Épaisseur de l’isolation (mils) (mm) | Diameter Over Shield (in) (cm) | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Rayon de courbure (pouces) (centimètres) | Conduit Size (in) (cm) | |
More Options |
1/0 AWG 1/0 AWG
|
19 19
|
0.361 0.92
|
1.240 3.15
|
420 10.67
|
1.300 3.30
|
80 2.03
|
1.480 3.76
|
1249 1859
|
844 382.83
|
17.7 44.96
|
4.5 11.43
|
More Options |
2/0 AWG 2/0 AWG
|
19 19
|
0.405 1.03
|
1.284 3.26
|
420 10.67
|
1.344 3.41
|
80 2.03
|
1.524 3.87
|
1377 2049
|
1064 482.62
|
18.2 46.23
|
4.5 11.43
|
More Options |
4/0 AWG 4/0 AWG
|
19 19
|
0.512 1.30
|
1.390 3.53
|
420 10.67
|
1.450 3.68
|
80 2.03
|
1.630 4.14
|
1721 2561
|
1692 767.48
|
19.6 49.78
|
4.5 11.43
|
More Options |
250 KCMIL 250 KCMIL
|
37 37
|
0.558 1.42
|
1.428 3.63
|
420 10.67
|
1.488 3.78
|
110 2.79
|
1.728 4.39
|
1983 2951
|
2000 907.18
|
20.7 52.58
|
5.0 12.70
|
More Options |
350 KCMIL 350 KCMIL
|
37 37
|
0.661 1.68
|
1.527 3.88
|
420 10.67
|
1.587 4.03
|
110 2.79
|
1.827 4.64
|
2385 3549
|
2800 1270.06
|
21.9 55.63
|
5.5 13.97
|
More Options |
500 KCMIL 500 KCMIL
|
37 37
|
0.789 2.00
|
1.652 4.20
|
420 10.67
|
1.712 4.35
|
110 2.79
|
1.952 4.96
|
2976 4429
|
4000 1814.37
|
23.4 59.44
|
5.5 13.97
|
More Options |
750 KCMIL 750 KCMIL
|
61 61
|
0.968 2.46
|
1.864 4.73
|
420 10.67
|
1.924 4.89
|
110 2.79
|
2.164 5.50
|
3972 5911
|
6000 2721.55
|
25.9 65.79
|
6.0 15.24
|
More Options |
1250 KCMIL 1250 KCMIL
|
91 91
|
1.250 3.18
|
2.150 5.46
|
420 10.67
|
2.210 5.61
|
110 2.79
|
2.450 6.22
|
5816 8655
|
10000 4535.92
|
29.4 74.68
|
|
More Options |
250 KCMIL 250 KCMIL
|
37 37
|
0.558 1.42
|
1.428 3.63
|
420 10.67
|
1.488 3.78
|
110 2.79
|
1.728 4.39
|
1975 2939
|
2000 907.18
|
20.7 52.58
|
5.0 12.70
|
* Conduit size based on 3 phase 40% fill-factor without ground
^ Non SimPull Jacket. Non CSA listed.
Cond. Dimensions | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
More Options |
1/0 AWG 1/0 AWG
|
0.102 0.15
|
0.128 0.19
|
0.064 0.10
|
0.054 0.08
|
0.465 + j0.274 0.465 + j0.274
|
0.129 + j0.054 0.129 + j0.054
|
4055 4055
|
200 200
|
215 215
|
260 260
|
290 290
|
More Options |
2/0 AWG 2/0 AWG
|
0.081 0.12
|
0.102 0.15
|
0.060 0.09
|
0.052 0.08
|
0.434 + j0.263 0.434 + j0.263
|
0.103 + j0.052 0.103 + j0.052
|
4192 4192
|
230 230
|
245 245
|
300 300
|
330 330
|
More Options |
4/0 AWG 4/0 AWG
|
0.051 0.08
|
0.065 0.10
|
0.050 0.07
|
0.048 0.07
|
0.387 + j0.237 0.387 + j0.237
|
0.066 + j0.049 0.066 + j0.049
|
4523 4523
|
295 295
|
315 315
|
395 395
|
445 445
|
More Options |
250 KCMIL 250 KCMIL
|
0.043 0.06
|
0.056 0.08
|
0.049 0.07
|
0.048 0.07
|
0.372 + j0.227 0.372 + j0.227
|
0.057 + j0.048 0.057 + j0.048
|
4690 4690
|
325 325
|
345 345
|
440 440
|
490 490
|
More Options |
350 KCMIL 350 KCMIL
|
0.031 0.05
|
0.041 0.06
|
0.044 0.07
|
0.045 0.07
|
0.347 + j0.207 0.347 + j0.207
|
0.042 + j0.045 0.042 + j0.045
|
5009 5009
|
390 390
|
415 415
|
545 545
|
605 605
|
More Options |
500 KCMIL 500 KCMIL
|
0.022 0.03
|
0.030 0.04
|
0.039 0.06
|
0.043 0.06
|
0.324 + j0.187 0.324 + j0.187
|
0.031 + j0.043 0.031 + j0.043
|
5406 5406
|
465 465
|
500 500
|
680 680
|
755 755
|
More Options |
750 KCMIL 750 KCMIL
|
0.014 0.02
|
0.023 0.03
|
0.034 0.05
|
0.040 0.06
|
0.3 + j0.161 0.3 + j0.161
|
0.024 + j0.04 0.024 + j0.04
|
5992 5992
|
565 565
|
610 610
|
870 870
|
970 970
|
More Options |
1250 KCMIL 1250 KCMIL
|
0.009 0.01
|
0.018 0.03
|
0.028 0.04
|
0.037 0.06
|
0.271 - j0.124 0.271 - j0.124
|
0.019 - j0.219 0.019 - j0.219
|
6878 6878
|
715 715
|
770 770
|
1185 1185
|
1320 1320
|
More Options |
250 KCMIL 250 KCMIL
|
0.043 0.06
|
0.056 0.08
|
0.049 0.07
|
0.048 0.07
|
0.372 + j0.227 0.372 + j0.227
|
0.057 + j0.048 0.057 + j0.048
|
4690 4690
|
325 325
|
345 345
|
440 440
|
490 490
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.