RHINOPOWERTM Type MP-GC mine power feeder cable is a heavy-duty power cable for use in stationary horizontal HV mine power distribution circuits, for permanent or semi-portable applications with power transmission in deep mines, surface mines, open pits, tunnels, in conduit or duct (not to exceed max rated voltage), and suitable for direct burial in wet or dry locations. Veuillez consulter un spécialiste en installation d’usine pour les exigences relatives aux chutes verticales.
Cond. Dimensions | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Épaisseur de l’isolation (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground Check Size | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
2 AWG 2 AWG
|
3 3
|
7 7
|
0.268 0.68
|
115 2.92
|
0.528 1.34
|
8 8
|
115 2.92
|
1.565 3.98
|
1637 2436
|
More Options |
4/0 AWG 4/0 AWG
|
3 3
|
19 19
|
0.474 1.20
|
115 2.92
|
0.735 1.87
|
8 8
|
145 3.68
|
2.120 5.38
|
3188 4744
|
More Options |
500 KCMIL 500 KCMIL
|
3 3
|
37 37
|
0.735 1.87
|
115 2.92
|
0.996 2.53
|
8 8
|
140 3.56
|
2.750 6.99
|
7880 11727
|
* Strand count meets minimum number per ASTM
Cond. Dimensions | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Puissance nominale (lbs) (kg) | Min. Rayon de courbure (pouces) (centimètres) | Allowable Ampacity In Air 90C | |
More Options |
2 AWG 2 AWG
|
0.162 0.24
|
0.204 0.30
|
0.046 0.07
|
0.037 0.06
|
453 205.48
|
18.7 47.50
|
159 159
|
More Options |
4/0 AWG 4/0 AWG
|
0.051 0.08
|
0.065 0.10
|
0.029 0.04
|
0.032 0.05
|
1447 656.35
|
25.4 64.52
|
321 321
|
More Options |
500 KCMIL 500 KCMIL
|
0.022 0.03
|
0.030 0.04
|
0.020 0.03
|
0.029 0.04
|
3420 1551.28
|
33.0 83.82
|
536 536
|
* Ampacities based upon ICEA S-75-381 Table I-1.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.