SPEC: 45158

CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2 Shielded. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER, PLTC, FPL, and NFPL Control Cable 600 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation THHN/THWN Polyvinyl Chloride (PVC) Jacket, Shielded Control Cable Conductor Identification Method 1 Table 2

Télécharger les spécifications de la catégorie
PDF Tableau Excel

Application & Features

Les câbles de contrôle de type TC-ER, PLTC, FPL et NFPL de Southwire conviennent pour une utilisation en zones humides et sèches, conduits, gaines, passages, chemins, en enfouissement direct pour les applications aériennes supportées par un porteur et où des propriétés électriques supérieures sont désirées. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in dry locations and 75°C in wet locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III per NEC Article 725 and 760. Les constructions UL avec 3 conducteurs ou plus sont homologuées pour les circuits exposés (TC-ER) conformément à l’article 336.10 du NEC. Oil and sunlight resistant.

Spécifications

Pour plus d’informations, sélectionnez un ensemble de produits ci-dessous :
Cond. Dimensions Conductor Number Cond. Strands Épaisseur de l’isolation (mils) (mm) Épaisseur de la jaquette (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Min. Rayon de courbure (pouces) (centimètres) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
14 AWG 14 AWG
2 2
7 7
15 0.38
45 1.14
0.323 0.82
33 49
66 98
2.631 3.92
3.170 4.72
1.3 3.30
20 20
25 25
More Options
12 AWG 12 AWG
4 4
7 7
15 0.38
45 1.14
0.422 1.07
93 138
148 220
1.662 2.47
2.002 2.98
1.7 4.32
20 20
24 24
More Options
10 AWG 10 AWG
5 5
7 7
20 0.51
45 1.14
0.588 1.49
182 271
288 429
1.040 1.55
1.253 1.86
2.4 6.10
28 28
32 32

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Normes et références

  • ASTM B3 Soft or Annealed Copper Wire
  • Conducteurs en cuivre toronné à couche concentrique ASTM B8
  • UL 13 Power-Limited Circuit Cables
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 TC-ER
  • UL 1685 Test de propagation des flammes et émission de fumées sur chemin vertical
  • Norme ICEA S-73-532 pour les câbles de contrôle, d’extension thermocouple et d’instrumentation
  • ICEA S-95-658 (NEMA WC70) Câbles d’alimentation à utiliser sous 2 000 volts ou moins pour la distribution d’électricité
  • EPA 40 CFR, Partie 26, Métaux lourds de la sous-partie C du tableau 1, méthode TCLP

Construction

  1. Conducteur : 7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Isolation : Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Drain Wire: Cuivre étamé
  4. Blindage : 100% coverage aluminum foil
  5. Jaquette : Polyvinyl Chloride (PVC) Jacket