For use in residential, farm and industrial water well applications. Used in both Grounded and ungrounded water well cable systems. Conductors are parallel and insulated with PVC colored black, red, and yellow. Insulated and jacketed with a premium thermoplastic elastomer (TPE) material. Oil resistant. Utilisé dans des puits à basse et haute température
Cond. Dimensions | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Épaisseur de l’isolation (mils) (mm) | Épaisseur de la jaquette (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
14 AWG 14 AWG
|
3 3
|
41 41
|
0.073 0.19
|
30 0.76
|
25 0.64
|
0.188 x 0.464 0.48 x 1.18
|
37 55
|
65 97
|
More Options |
14 AWG 14 AWG
|
4 4
|
41 41
|
0.073 0.19
|
30 0.76
|
25 0.64
|
0.188 x 0.602 0.48 x 1.53
|
50 74
|
87 129
|
More Options |
12 AWG 12 AWG
|
3 3
|
65 65
|
0.094 0.24
|
30 0.76
|
25 0.64
|
0.206 x 0.518 0.52 x 1.32
|
60 89
|
94 140
|
More Options |
12 AWG 12 AWG
|
4 4
|
65 65
|
0.094 0.24
|
30 0.76
|
25 0.64
|
0.206 x 0.674 0.52 x 1.71
|
80 119
|
126 188
|
More Options |
10 AWG 10 AWG
|
3 3
|
105 105
|
0.117 0.30
|
30 0.76
|
25 0.64
|
0.231 x 0.593 0.59 x 1.51
|
96 143
|
136 202
|
More Options |
10 AWG 10 AWG
|
4 4
|
105 105
|
0.117 0.30
|
30 0.76
|
25 0.64
|
0.231 x 0.774 0.59 x 1.97
|
128 190
|
181 269
|
More Options |
8 AWG 8 AWG
|
4 4
|
168 168
|
0.153 0.39
|
45 1.14
|
30 0.76
|
0.316 x 1.010 0.80 x 2.57
|
188 280
|
289 430
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
* Cond. Number does not include ground conductor.
Cond. Dimensions | Conductor Number | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Max Pull Tension (lbs) (kg) | Min. Rayon de courbure (pouces) (centimètres) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C |
14 AWG 14 AWG
|
3 3
|
2.814 4.19
|
3.391 5.05
|
0.058 0.09
|
98 44.45
|
1.9 4.83
|
20 20
|
25 25
|
14 AWG 14 AWG
|
4 4
|
2.814 4.19
|
3.391 5.05
|
0.058 0.09
|
105 47.63
|
2.4 6.10
|
16 16
|
20 20
|
12 AWG 12 AWG
|
3 3
|
1.774 2.64
|
2.137 3.18
|
0.054 0.08
|
156 70.76
|
2.1 5.33
|
25 25
|
30 30
|
12 AWG 12 AWG
|
4 4
|
1.774 2.64
|
2.137 3.18
|
0.054 0.08
|
167 75.75
|
2.7 6.86
|
20 20
|
24 24
|
10 AWG 10 AWG
|
3 3
|
1.111 1.65
|
1.339 1.99
|
0.050 0.07
|
249 112.94
|
2.4 6.10
|
35 35
|
40 40
|
10 AWG 10 AWG
|
4 4
|
1.111 1.65
|
1.339 1.99
|
0.050 0.07
|
265 120.20
|
3.1 7.87
|
28 28
|
32 32
|
8 AWG 8 AWG
|
4 4
|
0.715 1.06
|
0.861 1.28
|
0.052 0.08
|
422 191.42
|
5.0 12.70
|
40 40
|
44 44
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.