For use in residential, farm and industrial water well applications. Used in both Grounded and ungrounded water well cable systems. Conductors are parallel and insulated with PVC colored black, red, and yellow. Insulated and jacketed with a premium thermoplastic elastomer (TPE) material. Oil resistant. Utilisé dans des puits à basse et haute température
Cond. Dimensions | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Couleur | Épaisseur de l’isolation (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
12 AWG 12 AWG
|
4 4
|
19 19
|
0.090 0.23
|
PVC PVC
|
45 1.14
|
0.494 1.25
|
81 121
|
150 223
|
More Options |
10 AWG 10 AWG
|
4 4
|
19 19
|
0.117 0.30
|
PVC PVC
|
45 1.14
|
0.550 1.40
|
129 192
|
208 310
|
More Options |
8 AWG 8 AWG
|
4 4
|
19 19
|
0.143 0.36
|
PVC PVC
|
60 1.52
|
0.670 1.70
|
186 277
|
306 455
|
More Options |
6 AWG 6 AWG
|
4 4
|
19 19
|
0.179 0.45
|
PVC PVC
|
60 1.52
|
0.764 1.94
|
296 440
|
446 664
|
More Options |
4 AWG 4 AWG
|
4 4
|
19 19
|
0.226 0.57
|
PVC PVC
|
60 1.52
|
0.856 2.17
|
442 658
|
614 914
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
* Cond. Number does not include ground conductor.
Cond. Dimensions | Conductor Number | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Max Pull Tension (lbs) (kg) | Min. Rayon de courbure (pouces) (centimètres) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C |
12 AWG 12 AWG
|
4 4
|
1.662 2.47
|
2.002 2.98
|
0.054 0.08
|
167 75.75
|
2.0 5.08
|
20 20
|
24 24
|
10 AWG 10 AWG
|
4 4
|
1.040 1.55
|
1.253 1.86
|
0.050 0.07
|
265 120.20
|
2.2 5.59
|
28 28
|
32 32
|
8 AWG 8 AWG
|
4 4
|
0.653 0.97
|
0.786 1.17
|
0.052 0.08
|
422 191.42
|
2.7 6.86
|
40 40
|
44 44
|
6 AWG 6 AWG
|
4 4
|
0.411 0.61
|
0.495 0.74
|
0.051 0.08
|
671 304.36
|
3.1 7.87
|
52 52
|
60 60
|
4 AWG 4 AWG
|
4 4
|
0.258 0.38
|
0.310 0.46
|
0.048 0.07
|
1068 484.44
|
3.4 8.64
|
68 68
|
76 76
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.