SPEC: 48203

1/C CU 2000V NL-EPR RHH/RHW-2 Thermoset SOLONON LSZH-TS TRACTION POWER CABLE

Traction Power Cable 2000 Volt Single Conductor Copper, No Lead Ethylene Propylene Rubber (NL-EPR) insulation RHH/RHW-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket

Télécharger les spécifications de la catégorie
PDF Tableau Excel

Application & Features

Southwire 2000V No Lead NL-EPR/SOLONON Traction Power Cable is suited for use in mass transit and general industry applications where flexibility, fire resistance, and low smoke generation are a concern. May be installed in wet or dry locations in cable trays or raceways. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Resistance to moisture and most oils, acids, and alkalis with an overall durable LSZH XLPO jacket. Meets Flame Spread and Smoke Release requirements of NFPA 130. Classé pour 454 kg./Pression latérale maximale FT. Alternate constructions available upon request.

Spécifications

Pour plus d’informations, sélectionnez un ensemble de produits ci-dessous :
Cond. Dimensions Cond. Strands Strand Class Conductor Number Diameter Over Conductor (in) (cm) Épaisseur de l’isolation (mils) (mm) Épaisseur de la jaquette (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) DC Resistance at 25C (ohms/1000') (ohms/km) Max Pull Tension (lbs) (kg)
More Options
350 KCMIL 350 KCMIL
37 37
B B
1 1
0.641 1.63
75 1.91
65 1.65
0.944 2.40
1296 1929
0.031 0.05
2800 1270.06
More Options
500 KCMIL 500 KCMIL
37 37
B B
1 1
0.766 1.95
75 1.91
65 1.65
1.063 2.70
1791 2665
0.022 0.03
4000 1814.37
More Options
1000 KCMIL 1000 KCMIL
127 127
D D
1 1
1.118 2.84
90 2.29
65 1.65
1.450 3.68
3468 5161
0.011 0.02
8000 3628.74

Thicknesses shown as Minimum Average values

Normes et références

  • ASTM B3 Soft or Annealed Copper Wire
  • Conducteurs en cuivre toronné à couche concentrique ASTM B8
  • Spécification ASTM B172 relative aux conducteurs en cuivre toronnés à pose de câble ayant des conducteurs en cuivre toronnés en bande
  • ASTM B173 Rope-Lay-Stranded Copper Conductors Having Concentric-Stranded Members
  • UL 44 Fils et câbles à isolation thermo
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-95-658 (NEMA WC70) Câbles d’alimentation à utiliser sous 2 000 volts ou moins pour la distribution d’électricité
  • Test de résistance aux flammes sur chemin de câbles vertical IEEE 1202 FT4 (70 000 Btu/h)
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (250kcmil & Larger)

Construction

  1. Conducteur : Stranded bare copper per ASTM B3. Center strand embossed with “Southwire, Year, Plant” when required
  2. Binder Tape: Mylar Tape
  3. Isolation : No Lead Ethylene Propylene Rubber (NLEPR)
  4. Overall Jacket: Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket