For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Résistant au soleil. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
Cond. Taille | Calibre 14 AWG Calibre 14 AWG | |
Cond. Strands | 7 7 | |
Diameter Over Conductor (po) (cm) | 0.070 0.18 | po cm |
Épaisseur de l’isolation (mils) (mm) | 30 0.76 | mils mm |
Ground Size | 1x14 1x14 | |
Inner Jacket Thickness (mils) (mm) | 65 1.65 | mils mm |
Diameter Over Armor (po) (cm) | 0.774 1.97 | po cm |
Épaisseur de la jaquette (mils) (mm) | 45 1.14 | mils mm |
Approx. OD (po) (cm) | 0.864 2.19 | po cm |
Approx. Poids (lbs/1 000 pi) (kg/km) | 377 561 | lbs/1 000 pi kg/km |
Max Pull Tension (lbs) (kg) | 263 119.29 | lbs kg |
Min. Rayon de pliage (po) (cm) | 6.0 15.24 | po cm |
* Use Table 5C in the 2015 Canadian Electrical Code to derate this ampacity as per Rules 4-004 & 12-2210
† Ampacities based on not more than 3 conductors (4 with neutral) in raceway or cable as per Table 2 of 2015 Canadian Electrical Code