For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Résistant au soleil. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
Cond. Taille | Calibre 10 AWG Calibre 10 AWG | |
Cond. Strands | 7 7 | |
Diameter Over Conductor (po) (cm) | 0.113 0.29 | po cm |
Épaisseur de l’isolation (mils) (mm) | 30 0.76 | mils mm |
Ground Size | 1x12 1x12 | |
Inner Jacket Thickness (mils) (mm) | 85 2.16 | mils mm |
Diameter Over Armor (po) (cm) | 1.307 3.32 | po cm |
Épaisseur de la jaquette (mils) (mm) | 45 1.14 | mils mm |
Approx. OD (po) (cm) | 1.397 3.55 | po cm |
Approx. Poids (lbs/1 000 pi) (kg/km) | 1067 1588 | lbs/1 000 pi kg/km |
Max Pull Tension (lbs) (kg) | 1245 564.72 | lbs kg |
Min. Rayon de pliage (po) (cm) | 9.7 24.64 | po cm |
* Use Table 5C in the 2015 Canadian Electrical Code to derate this ampacity as per Rules 4-004 & 12-2210
† Ampacities based on not more than 3 conductors (4 with neutral) in raceway or cable as per Table 2 of 2015 Canadian Electrical Code