SPEC: 10000

8-19 SD CU SIMpull (TM) THHN-THWN-2 MTW-AWM PURPLE 1000 FT

N° Southwire : 25658602

Télécharger les spécifications de la catégorie
PDF Tableau Excel
Sélectionnez les spécifications du produit
Construction
Couleur de la jaquette externe / l’armure
NOIR
BLEU
MARRON
GRIS
VERT
ORANGE
ROSE
VIOLET
ROUGE
BRONZÉ
BLANC
JAUNE
Format

Application & Features

Southwire SIMpull® THHN/THWN-2 copper conductors are primarily used in conduit and cable trays for services, feeders, and branch circuits in commercial or industrial applications as specified in the National Electrical Code® and other applicable codes and standards. La tension nominale pour toutes les installations est de 600 volts. SIMpull® THHN/THWN-2 copper conductors are designed to be installed without the application of a pulling lubricant. These conductors have multiple ratings depending upon the product application. Les températures admissibles sont les suivantes :
- THHN or T90 Nylon- Dry locations not to exceed 90°C
- THWN-2- Wet or dry locations not to exceed 90° C or locations not to exceed 75°C when exposed to oil
- TWN75- Wet locations not to exceed 75°C
- MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
- AWM- Dry locations not to exceed 105°C only when rated and used as appliance wiring material

CARACTÉRISTIQUES
- Sunlight resistant #8 AWG and larger
- Gasoline and Oil Resistant II
- CT Rated 1/0 AWG and Larger
- VW-1 All Sizes
- FT-1 All Sizes
- AWM- Sizes 14 through 6 AWG
- MTW- Stranded Constructions Only
- RoHS Compliant
- LEED v4.1 Materials & Resources Credit MRc6; PBT (Lead Content Below 300 ppm Threshold)

Spécifications

Cond. Taille Calibre 8 AWG Calibre 8 AWG
Conductor Number 1 1
Cond. Strands 19 19
Diameter Over Conductor (po) (cm) 0.143 0.36 po cm
Épaisseur de l’isolation (mils) (mm) 31 0.79 mils mm
Épaisseur de la jaquette (mils) (mm) 6 0.15 mils mm
Approx. OD (po) (cm) 0.217 0.55 po cm
Copper Weight (lbs/1 000 pi) (kg/km) 50 74 lbs/1 000 pi kg/km
Approx. Poids (lbs/1 000 pi) (kg/km) 63 94 lbs/1 000 pi kg/km

Normes et références

  • Conducteurs en cuivre toronné à couche concentrique ASTM B8
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material
  • UL 1063 Câblage des machines-outils (MTW)
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables
  • ICEA S-95-658 (NEMA WC70) Câbles d’alimentation à utiliser sous 2 000 volts ou moins pour la distribution d’électricité
  • Spécification fédérale A-A-59544
  • NMX-J-010-ANCE Thermoplastic insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements

Construction

  1. Conducteur : Stranded sizes #8 AWG - 3/0 AWG use a combination-unilay stranded soft drawn bare copper per ASTM B787. Sizes 4/0 AWG and larger use compressed stranded bare copper per ASTM B8
  2. Isolation : Heat and moisture resistant PVC
  3. Sheath: Nylon jacket utilizing SIMpull Technology