SPEC: 10000

600-61 SD CU SIMpull (TM) THHN-THWN-2 MTW BROWN 1500 FT

N° Southwire : 55618103

Télécharger les spécifications de la catégorie
PDF Tableau Excel
Sélectionnez les spécifications du produit
Construction
Couleur de la jaquette externe / l’armure
NOIR
BLEU
MARRON
GRIS
VERT
ORANGE
ROSE
VIOLET
ROUGE
BRONZÉ
BLANC
JAUNE
Format

Application & Features

Southwire SIMpull® THHN/THWN-2 copper conductors are primarily used in conduit and cable trays for services, feeders, and branch circuits in commercial or industrial applications as specified in the National Electrical Code® and other applicable codes and standards. La tension nominale pour toutes les installations est de 600 volts. SIMpull® THHN/THWN-2 copper conductors are designed to be installed without the application of a pulling lubricant. These conductors have multiple ratings depending upon the product application. Les températures admissibles sont les suivantes :
- THHN or T90 Nylon- Dry locations not to exceed 90°C
- THWN-2- Wet or dry locations not to exceed 90° C or locations not to exceed 75°C when exposed to oil
- TWN75- Wet locations not to exceed 75°C
- MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
- AWM- Dry locations not to exceed 105°C only when rated and used as appliance wiring material

CARACTÉRISTIQUES
- Sunlight resistant #8 AWG and larger
- Gasoline and Oil Resistant II
- CT Rated 1/0 AWG and Larger
- VW-1 All Sizes
- FT-1 All Sizes
- AWM- Sizes 14 through 6 AWG
- MTW- Stranded Constructions Only
- RoHS Compliant
- LEED v4.1 Materials & Resources Credit MRc6; PBT (Lead Content Below 300 ppm Threshold)

Spécifications

Cond. Taille 600 KCMIL 600 KCMIL
Conductor Number 1 1
Cond. Strands 61 61
Diameter Over Conductor (po) (cm) 0.865 2.20 po cm
Épaisseur de l’isolation (mils) (mm) 70 1.78 mils mm
Épaisseur de la jaquette (mils) (mm) 10 0.25 mils mm
Approx. OD (po) (cm) 1.030 2.62 po cm
Copper Weight (lbs/1 000 pi) (kg/km) 1852 2756 lbs/1 000 pi kg/km
Approx. Poids (lbs/1 000 pi) (kg/km) 1992 2964 lbs/1 000 pi kg/km

Normes et références

  • Conducteurs en cuivre toronné à couche concentrique ASTM B8
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material
  • UL 1063 Câblage des machines-outils (MTW)
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables
  • ICEA S-95-658 (NEMA WC70) Câbles d’alimentation à utiliser sous 2 000 volts ou moins pour la distribution d’électricité
  • Spécification fédérale A-A-59544
  • NMX-J-010-ANCE Thermoplastic insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements

Construction

  1. Conducteur : Stranded sizes #8 AWG - 3/0 AWG use a combination-unilay stranded soft drawn bare copper per ASTM B787. Sizes 4/0 AWG and larger use compressed stranded bare copper per ASTM B8
  2. Isolation : Heat and moisture resistant PVC
  3. Sheath: Nylon jacket utilizing SIMpull Technology
Powered by Translations.com GlobalLink Web Software