SPEC: 25030

2-7 3/C CU EPR TECK90 5KV N/S AIA ORANGE PVC JKT

N° Southwire : 56846799

Télécharger les spécifications de la catégorie
PDF Tableau Excel
Sélectionnez les spécifications du produit
Construction
Couleur de la jaquette externe / l’armure
ORANGE
Format

Application & Features

Southwire’s 5KV TECK 90, 5000V, non-shielded, EPR insulated power cable is a CSA approved armoured cable for industrial and commercial medium voltage applications. FT4, -40°C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and is concrete encaseable.

  • -40°C - CSA Cold Bend and Impact Temperature
  • -25°C - Min. Installation Temperature
  • 90°C - Max. Continuous Operating Temperature
  • 140°C for Emergency Overload Temperature
  • 250°C for Short Circuit Temperature

Spécifications

Cond. Taille Calibre 2 AWG Calibre 2 AWG
Cond. Strands 7 7
Diameter Over Conductor (po) (cm) 0.282 0.72 po cm
Épaisseur de l’isolation (mils) (mm) 90 2.29 mils mm
Ground Size 1x6 1x6
Inner Jacket Thickness (mils) (mm) 85 2.16 mils mm
Diameter Over Armor (po) (cm) 1.585 4.03 po cm
Épaisseur de la jaquette (mils) (mm) 55 1.40 mils mm
Approx. OD (po) (cm) 1.695 4.31 po cm
Approx. Poids (lbs/1 000 pi) (kg/km) 1541 2293 lbs/1 000 pi kg/km
Max Pull Tension (lbs) (kg) 1592 722.12 lbs kg
Min. Rayon de pliage (po) (cm) 11.8 29.97 po cm

* Other conductor sizes and outer jacket colours are available upon request. (#s in brackets represent # of strands / conductor. Number of strands may vary as per CSA standard.)

Normes et références

  • ASTM B3 Soft or Annealed Copper Wire
  • Conducteurs en cuivre toronné à couche concentrique ASTM B8
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Câbles non-blindés
  • Test de résistance aux flammes IEEE 383 (70 000 btu)
  • Test de résistance aux flammes sur chemin de câbles vertical IEEE 1202 FT4 (70 000 Btu/h)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)

Construction

  1. Conducteur : Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
  2. Conductor Shield: Extruded semi-conducting thermosetting polymeric layer
  3. Isolation : No-Lead EPR (ethylene propylene rubber), Thickness: 0.090” (2.3 mm) - nominal, 90°C
  4. Grounding Conductor: Class B compressed or compact stranded bare copper, in accordance with ASTM B3 and B8
  5. Liaison/attache : Polypropylene tape
  6. Inner Jacket: Black PVC, Thickness: No. 2 AWG to No. 3/0 AWG = 0.080” (2.0 mm); No. 4/0 AWG to 500 kcmil = 0.110” (2.8 mm); 750 kcmil to 1000 kcmil = 0.140” (3.6 mm)
  7. Armor: Aluminum Interlocked Armour (AIA)
  8. Overall Jacket: Orange PVC (optional colours available), Thickness: No. 2 AWG to 250 kcmil = 0.060” (1.5 mm); 350 kcmil to 750 kcmil = 0.075” (1.9 mm); 1000 kcmil = 0.090” (2.3 mm)

Ressources

Il n’existe aucune ressource téléchargeable pour ce produit.
Powered by Translations.com GlobalLink Web Software